3.

Incineration and co-incineration plants shall have and operate an automatic system to prevent waste feed: at start-up, until the temperature of 850 °C or 1100 °C as the case may be or the temperature specified according to paragraph 4 has been reached; whenever the temperature of 850 °C or 1100 °C as the case may be or the temperature specified according to paragraph 4 is not maintained; whenever the continuous measurements required by this Directive show that any emission limit value is exceeded due to disturbances or failures of the purification devices.