NEW CLASS B, C AND D SHIPS:
Lighting fittings shall be so arranged as to prevent temperature rises which could damage the cables and wiring, and to prevent surrounding material from becoming excessively hot. Accumulator batteries shall be suitably housed, and compartments used primarily for their accommodation shall be properly constructed and efficiently ventilated. Electrical or other equipment which may constitute a source of ignition of flammable vapours shall not be permitted in these compartments. Distribution systems shall be so arranged that fire in any main vertical zone, as defined in Regulation II-2/A/2.9, will not interfere with services essential for safety in any other such zone. This requirement will be met if main and emergency feeders passing through any such zone are separated both vertically and horizontally as widely as is practicable.