NEW CLASS B, C AND D SHIPS:
Ships carrying more than 36 passengers shall have the detection alarms for the systems required by Regulation 13.2 centralised in a continuously manned central control station. In addition, controls for remote closing of the fire doors and shutting down the ventilation fans, shall be centralised in the same location. The ventilation fans shall be capable of reactivation by the crew at the continuously manned control station. The control panel in the central control station shall be capable of indicating open or closed positions of fire doors, closed or off status of the detectors, alarms and fans. The control panel shall be continuously powered and should have an automatic changeover to standby power supply in case of loss of normal power supply. The control panel shall be powered from the main source of electrical power and the emergency source of electrical power defined by Regulation II-1/D/3 unless other arrangements are permitted by the regulations, as applicable. The control panel shall be designed on the fail-safe principle, e.g. an open detector circuit shall cause an alarm condition.