IED

3.1. | The following measurements shall be carried out at the point of waste water discharge: (a) continuous measurements of pH, temperature and flow; (b) spot sample daily measurements of total suspended solids or measurements of a flow proportional representative sample over a period of 24 hours; (c) at least monthly measurements of a flow proportional representative sample of the discharge over a period of 24 hours of Hg, Cd, TI, As, Pb, Cr, Cu, Ni and Zn; (d) at least every 6 months measurements of dioxins and furans; however, one measurement at least every 3 months shall be carried out for the first 12 months of operation.