1. CE marking and inscriptions

Vessels of which the product of PS × V exceeds 50 bar.L must bear the CE marking provided for in Annex II of Regulation (EC) No 765/2008 and the last two digits of the year in which the CE marking was affixed. Vessels or their data plates shall bear at least the following information: the maximum working pressure (PS in bar); the maximum working temperature (T_(max) in °C); the minimum working temperature (T_(min) in °C); the capacity of the vessel (V in L); the name, registered trade name or registered trade mark and the address of the manufacturer; the type and serial or batch identification of the vessel. Where the data plate is used, it shall be so designed that it cannot be reused and shall include a vacant space to enable other information to be provided.