lexiara

anx_III__table_1

Text with EEA relevance.

Table 1 Frequency quality defining parameters of the synchronous areas CE GB IE/NI Nordic standard frequency range ± 50 mHz ± 200 mHz ± 200 mHz ± 100 mHz maximum instantaneous frequency deviation 800 mHz 800 mHz 1000 mHz 1000 mHz maximum steady-state frequency deviation 200 mHz 500 mHz 500 mHz 500 mHz time to recover frequency not used 1 minute 1 minute not used frequency recovery range not used ± 500 mHz ± 500 mHz not used time to restore frequency 15 minutes 15 minutes 15 minutes 15 minutes frequency restoration range not used ± 200 mHz ± 200 mHz ± 100 mHz alert state trigger time 5 minutes 10 minutes 10 minutes 5 minutes