1.

Text with EEA relevance.

A transmission system shall be in the normal state when all of the following conditions are fulfilled: voltage and power flows are within the operational security limits defined in accordance with Article 25; frequency meets the following criteria: the steady state system frequency deviation is within the standard frequency range; or the absolute value of the steady state system frequency deviation is not larger than the maximum steady state frequency deviation and the system frequency limits established for the alert state are not fulfilled; active and reactive power reserves are sufficient to withstand contingencies from the contingency list defined in accordance with Article 33 without violating operational security limits; operation of the concerned TSO's control area is and will remain within operational security limits after the activation of remedial actions following the occurrence of a contingency from the contingency list defined in accordance with Article 33.