control voltage and manage reactive power by means of: tap changes of the power transformers; switching of the capacitors and reactors; switching of the power-electronics-based devices used for voltage and reactive power management; instructing transmission-connected DSOs and significant grid users to block automatic voltage and reactive power control of transformers or to activate on their facilities the remedial actions set out in points (i) to (iii) if voltage deterioration jeopardises operational security or threatens to lead to a voltage collapse in a transmission system; requesting the change of reactive power output or voltage setpoint of the transmission-connected synchronous power generating modules; requesting the change of reactive power output of the converters of transmission-connected non-synchronous power generating modules;