2.
Each TSO shall exchange with the other TSOs in its observability area the following data about its transmission system using real-time data exchanges between the TSOs' supervisory control and data acquisition (SCADA) systems and energy management systems: actual substation topology; active and reactive power in line bay, including transmission, distribution and lines connecting SGUs; active and reactive power in transformer bay, including transmission, distribution and SGUs connecting transformers; active and reactive power in power generating facility bay; regulating positions of transformers, including phase-shifting transformers; measured or estimated busbar voltage; reactive power in reactor and capacitor bay or from a static VAR compensator; and restrictions on active and reactive power supply capabilities with respect to the observability area.