Unless otherwise provided by the TSO, each DSO shall provide its TSO, in real-time, the information related to the observability area of the TSO as referred to in Article 43(1) and (2), including: the actual substation topology; the active and reactive power in line bay; the active and reactive power in transformer bay; the active and reactive power injection in power generating facility bay; the tap positions of transformers connected to the transmission system; the busbar voltages; the reactive power in reactor and capacitor bay; the best available data for aggregated generation per primary energy source in the DSO area; and the best available data for aggregated demand in the DSO area.