9. The putting into operation of the following electrical switchgear using, or whose functioning relies upon, fluorinated greenhouse gases in insulating or breaking medium shall be prohibited as follows: from 1 January 2026, medium voltage electrical switchgear for primary and secondary distribution up to and including 24 kV; from 1 January 2030, medium voltage electrical switchgear for primary and secondary distribution from more than 24 kV up to and including 52 kV; from 1 January 2028, high voltage electrical switchgear from 52 kV up to and including 145 kV and up to and including 50 kA short circuit current, with a global warming potential of 1 or more; from 1 January 2032, high voltage electrical switchgear of more than 145 kV or more than 50 kA short circuit current, with a global warming potential of 1 or more.