Table 1 Voltage ranges at the connection point between 110 kV and 300 kV Synchronous area Voltage range Continental Europe 0,90 pu-1,118 pu Nordic 0,90 pu-1,05 pu Great Britain 0,90 pu-1,10 pu Ireland and Northern Ireland 0,90 pu-1,118 pu Baltic 0,90 pu-1,118 pu