lexiara

anx_II__table_1__text_1

Text with EEA relevance.

Table 1 Voltage ranges at the connection point between 110 kV and 300 kV

· All articles ·

Source: EUR-Lex (Cellar) · retrieved 2026-11-04 · Text as adopted (Official Journal); later amendments are not incorporated in this text.